Basic parameters

- Rated voltage Ur 24kV

- Lightning impulse voltage 125kV

- Withstand voltage frequency vol. Ud 50 kV

- IP ratings IP4X

- Rated frequency fr 50Hz

- Rated current Ir 630A

- Rated short time withstand Ik 16kA

- Operating temperature range -5 ÷ 40ºC

- Rated peak withstand current 40kA

- Rated duration of short circuit tk 1s

- Class of resistance to internal arc IAC AFLR 16kA/1s